Fire Detection Control Panel
Series BC216
User Manual Part A
Description
Operating Instructions
Subject to change without notice
© by MEP - Gefahrenmeldetechnik GmbH. Pockau© by Labor Strauss Sicherungsanlagenbau Ges.m.b.H. Wien
Seitenansicht 0
1 2 3 4 5 6 ... 72 73

Inhaltsverzeichnis

Seite 1 - Series BC216

Fire Detection Control PanelSeries BC216User Manual Part ADescriptionOperating Instructions Subject to change without notice© by MEP - Gefahrenmeldete

Seite 2 - ZN5002/73/2

out the reconditioning. Together with the fire prevention officer you have to determine the additionalprotective measures that are to be taken until t

Seite 3 - Contents

Further approvals are in preparation.1.4 WarrantyYour fire detection control panel Series BC216 has been manufactured with greatest precision andcare.

Seite 4 - ZN5002/73/4

Delay timeThe delay time consists of reaction- and exploration time. During the reaction period the activationof the transmitting devices for fire ala

Seite 5 - ZN5002/73/5

LoopRing-shaped wiring with bi-directional data-bus to connect intelligent fire detectors (e.g., sensors,detectors) and actuation devices to the fire

Seite 6 - ZN5002/73/6

ing proper equipment for transmission (e.g., continually monitored telephone cables). The transmit-ting device for fire alarm messages which can also

Seite 7 - 1 Introduction

2 Fire detection control panel Series BC216The construction of a typical fire detection system, the most important features of the fire detectioncontr

Seite 8 - 1.1 Symbols and type fonts

2.2 Typical construction of a fire detection system with network control panelBCnet216Basically the network fire detection control panel BCnet216 does

Seite 9 - ZN5002/73/9

Basically all fire detectors and other devices that may be connected to a stand-alone control panel oftype BC216-1 may also be connected to every sing

Seite 10 - ZN5002/73/10

In case of an alarm, the user can explore the possible danger prior to the transmission of the fire alarmto the fire brigade by using the alarm delay

Seite 11 - 1.5 Special terms

for false fire alarms. The fire detection control panel BC216-1, besides automatic adjusting of the sen-sitivity of the detectors, is capable of displ

Seite 12 - ZN5002/73/12

HB216AE.SAM / 0130 / AN9161202ZN5002/73/22User Manual Series BC216 / Part AAll rights reserved. Under the copyright laws, no part of this manual or o

Seite 13 - ZN5002/73/13

played on the control panel. In addition to the zone number, the fire detection control panels SeriesBC216 are capable of displaying a zone-specific t

Seite 14 - ZN5002/73/14

2.4.4 ActuationsPractically any number of actuations can be activated by the fire detection control panels SeriesBC216. The activation of each actuati

Seite 15 - ZN5002/73/15

3 Displaying and operating elementsThe functions and effects of the displaying and operating elements of the fire detection control panelSeries BC216

Seite 16 - BCnet216

You operate the fire detection control panel Series BC216 with the clear and sturdy keypad on the frontof the case. An illuminated LC-display and ligh

Seite 17 - ZN5002/73/17

The third line displays the text information for the element of the current alarm. Is no element textprogrammed, the second text information for the z

Seite 18 - ZN5002/73/18

3.6 Reset-buttons'Panel reset'-button: All actual fire alarms, technical messages, fault alarms, faults and actuations arereset in one actio

Seite 19 - ZN5002/73/19

The displaying and operating elements of the field TRANSM. DEVICE 1 are reserved for the primarytransmitting device, which is exclusively designed for

Seite 20 - ZN5002/73/20

this is only possible by the use of the menu (see from page 43 in Chapter 4.7.10: "Displaying andoperating alarming devices - menu point [Alarmin

Seite 21 - ZN5002/73/21

330 21.12.2002 08:45 ENABLEMENT 0002 1.Floor Storage area331 21.12.2002 08:47 AUTHORIZATION EXIT User levelFigure 6: Example of a protocol print-outTh

Seite 22 - TRANSMITTING DEVICE 1 - field

4 Basic operation of the fire detection control panels Series BC216The basic functions of the fire detection control panels Series BC216, together wit

Seite 23 - 3.1 Info field

Contents1 Introduction...71.1 Symbols and type fonts ...

Seite 24 - 3.4 Numeric keys

By confirming the menu point [Exit authorization?], authorization level 2 is left. Has no operationoccurred for 15 minutes, the control panel returns

Seite 25 - 3.8 TRANSM. DEVICE 1 - field

During activities that require authorization level 4, the fire detection control panel is usuallycompletely out of service!4.2 Operations using single

Seite 26 - 3.9 ALARM. DEVICE 1 - field

With the possibility to reactivate the primary alarming device, you can repeat a prematurely inter-rupted evacuation alarm of a building without activ

Seite 27 - 3.12 Protocol printer

By exception of the primary transmitting device, all other transmitting devices are operated exclusivelyby the use of the menu. Only the primary trans

Seite 28 - ZN5002/73/28

the beginning of a code and leads you straight to the menu point [Authorization code:]. This hap-pens also if you are in a display-menu point such as,

Seite 29 - 4.1 Operating authorization

Authorization level 1 Authorization levels 2 and 3Main menu points Submenu points Main menu points Submenu pointsAlarms AlarmsActivated actuations Act

Seite 30 - ZN5002/73/30

4.5 Entering and exiting authorization level 2To enter authorization level 2 from authorization level 1, you have to enter the 4-digit user code pro-g

Seite 31 - ZN5002/73/31

The number of incorrect inputs is limited. After 5 incorrect inputs, the input of the installer-code islocked for 15 minutes.To return from authorizat

Seite 32 - ZN5002/73/32

4.7.2 Displaying activated actuations - menu point [Activated actuations]Scroll through all activated actuations by using the '↑↓'-buttons (

Seite 33 - 4.3 Operations using the menu

1.TECH.DIS 0003<zone text1><zone text2> Figure 11: Example for the display of the disablement of a technical message, zone 3.In this cas

Seite 34 - ZN5002/73/34

4.7.1 Displaying fire alarms - menu point [Alarms] ... 374.7.2 Displaying activated actuations - menu point [Acti

Seite 35 - ZN5002/73/35

No alarm is transmitted by detector zones that are disabled, faulted or put in test condition. A detectorzone that is disabled, faulted or put in test

Seite 36 - ZN5002/73/36

If the function "measured value/maintenance" is selected, the LC-display shows the measured value atthe time of function selection of this d

Seite 37 - ZN5002/73/37

The activation of an actuation for test purposes acts like a real activation! Consider that thismay lead to an unintended activation of an extinguishi

Seite 38 - ZN5002/73/38

If the parameters of the transmitting device have been set to take the device out of operation automati-cally in authorization level 2 or 3 (see from

Seite 39 - ZN5002/73/39

The event memory can be accessed by using the menu point [Event memory]. You can set one of thepossible filters [Display all], [Control panel] or [Det

Seite 40 - ZN5002/73/40

4.7.12.4 Correcting the clock time - submenu point [Clock time correction]The built-in quartz clock has an accuracy of a few seconds per year. In case

Seite 41 - ZN5002/73/41

4.7.12.9 Displaying the installed componentries - submenu point [Componentries]You can display the corresponding number of the software version and an

Seite 42 - ZN5002/73/42

With a single measured value print-out, the output of current events is suppressed until the print-outhas been finished. With the periodical measured

Seite 43 - ZN5002/73/43

4.8 Operating the control panel by using the fire brigade control unitA fire brigade control unit offers the fire brigade the possibility to operate t

Seite 44 - ZN5002/73/44

5 Operating conditions of fire detection control panels Series BC216This chapter describes the operating conditions of a fire detection control panel

Seite 45 - ZN5002/73/45

6.1.1 Testing of the fire detection control panel and the power supply devices ... 656.1.2 Testing of detectors ...

Seite 46 - ZN5002/73/46

By using the '↑↓'-buttons, you can browse in an event-category (e.g., in all current alarms); by usingthe '← →'-buttons, you can s

Seite 47 - ZN5002/73/47

No rules or instructions beyond those necessary for the operation of the control panel are given in thisUser Manual. You have to analyze the site-spec

Seite 48 - ZN5002/73/48

The activation of a transmitting device and of an alarming device are classified as an actuation andtherefore activate the red light-emitting diode &a

Seite 49 - ZN5002/73/49

The information on the transmission to the fire brigade and the sirens given in this chapter are onlyvalid for the common case that the panel was conf

Seite 50 - 5.2 Fire alarm condition

Starting at the display of alarms you can scroll to the main menu points [Faults] and [Disablements] byusing the '← →'-buttons. In these men

Seite 51 - ZN5002/73/51

5.2.5 Fire alarm condition - special case: alarm in an interdependence of two detectorsInterdependencies of two detectors can be set during planning f

Seite 52 - ZN5002/73/52

line will show the second zone text, if this is available. The fourth line is reserved for fire alarmmessages.If the parameters have been set accordin

Seite 53 - ZN5002/73/53

The internal buzzer is sounding constantly.You can silence the internal buzzer by using the button 'Silence buzzer'. The buzzer is activated

Seite 54 - ZN5002/73/54

display of the panel, the yellow light-emitting diode 'Technical message' and the buzzer are activatedby these messages also.Technical messa

Seite 55 - ZN5002/73/55

At a fault in the primary transmitting device or the primary alarming device, the corresponding yel-low LED-displays are flashing.At a fault in the po

Seite 56 - ZN5002/73/56

HB216AE.SAM / 0130 / AN9161202ZN5002/73/66User Manual Series BC216 / Part A

Seite 57 - ZN5002/73/57

ConditionEffectDisplaying (1st line)Fault in an element (e.g., Nr. 5) of a detector zone (e.g., Nr. 3) for technicalmessagesThe transmitting of an ala

Seite 58 - 5.5 Fault-message condition

The fire detection system is supplied with power by the stand-by battery in case of a fault with mainspower shut down. The required bridging time is r

Seite 59 - ZN5002/73/59

At disablement of the primary transmitting device or the primary alarming device, the correspond-ing yellow disablement-LED-displays are illuminated.T

Seite 60 - ZN5002/73/60

In case of several current disablements, you can tell the order of their occurrence by the number infront of the disablement message. Starting with th

Seite 61 - 5.6 Disablement condition

Additional information (e.g., date and time of the test procedure, the number of current test procedures,hints for operating the menu, hints for autho

Seite 62 - ZN5002/73/62

6 Ensuring the efficacy of the system by the userIn order to ensure the efficacy of the fire detection system the user periodically should make sure t

Seite 63 - 5.7 Test condition

After finishing the testing of the detectors you have to terminate the test condition immediately.Detection zones in test condition cannot transmit an

Seite 64 - ZN5002/73/64

6.3 Reconditioning and maintenanceParts of the system that have a fault are not able to perform their functions efficiently or at all. There-fore have

Seite 65 - 6.1 Periodic function tests

7 Event memory - entriesYou can browse in the event memory by the use of the '↑↓'-buttons. The first three lines of the LC-display show the

Seite 66 - 6.2 Other tests

Event Event text Text 2nd line Text 3rd line Additional text(info-button)Test condition offFLT.TEST.T 0001/001zone text 1 zo. text 2 / element textTe

Seite 67 - ZN5002/73/67

1 IntroductionDecades of research and development of LST in the field of fire detection control panel technology andthe successful cooperation with re

Seite 68 - 7 Event memory - entries

Event Event text Text 2nd line Text 3rd line Additional text(info-button)Test activation terminationAL-DEV.TEST.T 01alarming device text 1 alarming

Seite 69 - Alarming devices

Event Event text Text 2nd line Text 3rd line Additional text(info-button)Fault termination functionmodule 2FAULT.T FM2fault causeFault termination INF

Seite 70 - Control panel events

8 IndexActivation condition of actua-tions, 55Actuation, 21- Display, 38, 41- Light-emitting diode, 25- Operate, 41- Two-zone dependency, 56Alarm coun

Seite 71 - ZN5002/73/71

Software version, 8, 46Specifications, 67Stand-by battery, 18, 65- Disposal, 65Standards, 10System fault, 10, 25Technical message, 49, 56- Display, 38

Seite 72 - ZN5002/73/72

This User Manual is not designed as a description of or as an operating instruction for a fire detectionsystem. Therefore, detailed instructions for h

Seite 73 - ZN5002/73/73

in the expansion of the area surveilled require careful replanning and adaptation of the fire detectionsystem.The fire detection system has to be chec